Application and energy saving of plate heat exchanger in data center

1, water cooling system
From 2005 to 2009, the Internet industry developed rapidly, and the demand for data services soared. Data centers with small scale and low power density had to bear a lot of IT equipment. At this time, the power density of the single cabinet has increased to 3~5kw, and the size of the data center has gradually increased. Medium-sized data centers with hundreds to thousands of cabinets have begun to appear. As the scale has grown, data center energy consumption has increased dramatically, and energy conservation issues have begun to receive attention.
The traditional air-cooled direct expansion system has lower energy efficiency than COP (Coefficient Of Performance). The COP in Beijing is about 2.5~3.0. The air-conditioning equipment consumes a lot of power and accounts for a high proportion of the overall power consumption of the data center. Moreover, with the expansion of installed capacity, the installation position of the air-cooled condenser reserved in the original data center building is seriously insufficient, and the noise disturbance problem is prominent, which restricts the expansion of the data center. At this time, the chilled water system widely used in office buildings began to be gradually applied to the data center refrigeration system. Since the COP of the chiller can reach 3.0~6.0, the large centrifugal chiller is even higher, and the chilled water system can greatly reduce the data. The center operates energy consumption.
The chilled water system is mainly composed of a chiller, a cooling tower, a chilled water pump, a cooling water pump, and a chilled water type air conditioner end. The system adopts centralized cold source, the cooling efficiency of the chiller is high, and the cooling tower is placed in a flexible position, which can effectively control the noise and benefit the aesthetic appearance of the building. After reaching a certain scale, it has more construction cost and maintenance cost than the direct evaporative system. Economic advantage.
Cooling system
The end of the air-conditioning system used in the chilled water system is a chilled water-type precision air conditioner, and its single cooling capacity can reach more than 150kw. The air supply mode and the previous air-cooled direct expansion system have not changed much, only the cooling medium in the end changes. The air conditioning equipment is still far away from the IT heat source, and mainly relies on the air-conditioning fan to deliver air to maintain the airflow organization.
 2, plate heat exchanger and water cooling system natural cooling
From 2010 to the present, with the development of data center cooling technology and people's further attention and pursuit of data center energy consumption, the concept of natural cooling has gradually been applied to the data center.
In the northern part of China, the outdoor temperature is lower in winter, and the water side natural cooling system is used. In winter, there is no need to open the mechanical refrigeration unit, and the cooling tower and the plate heat exchanger are used to “free” to obtain the cold source, thereby reducing the energy consumption of the data center. The water side natural cooling system is a set of plate heat exchangers and related switching valve groups above the original chilled water system. The chiller mechanical cooling is still used in high temperature weather, and the low temperature cooling water prepared by the cooling tower is used in the low temperature season. The high-temperature chilled water is exchanged for heat. In the transitional season, the lower-temperature cooling water and the higher-temperature chilled water are pre-cooled before entering the chiller, and the chiller load and running time can be reduced.
Principle of natural cooling system for water cooling system
 
The temperature of chilled water in traditional data centers is generally 7/12 °C. For example, in Beijing, natural cooling can be used 39% of the year. If the chilled water is raised to 10/15 °C, the natural cooling time will be extended to 46%. At the same time, due to the increase of evaporation temperature, the COP of the chiller can be increased by 10%. On the other hand, as the server withstands the increase in temperature, the chilled water temperature can be further increased, and the natural cooling time throughout the year will be further extended. At present, the domestic technology-leading data center has increased the chilled water temperature to 15/21 °C, and the natural cooling time can reach 70% or even longer.
2019/05/10 20:04:16 3705 Click

小商品城:全资子公司获配沐曦股份57.33万股|小商品城 正邦科技:公司将加强与投资者的沟通和交流,提高服务意识|正邦科技 中信证券:推动人民币升值的因素逐渐增多 龙旗科技已举行香港上市聆讯,保荐人收到相关信函、但不构成正式的上市批准|香港 福晶科技:公司可以为客户提供飞秒等超快激光用的晶体、光学、器件相关产品|福晶科技 2026年贺岁纪念币和纪念钞来了,预约方式→ 早盘:美股走高科技股领涨 纳指上涨1.1% 酒价内参12月20日价格发布 市场整体上扬国窖1573领涨 A股深夜重磅!千亿级大并购来了 首换董事长!净利问鼎农险榜首、赔付率高达74%,中原农险如何续写新十年? 陕西首份自动签发《入境货物检验检疫证明》发出 上期能源:自2026年1月1日起至2026年12月31日暂免收取交割商品注册费 从赛道王者到生态筑基者:领克汽车运动2.0时代的战略升维|汽车 刘世锦:中国经济增长由供给约束转向需求约束 东方徐来 花丝世家 透视药明康德:长期主义与基本面信心才是关键 珠江委与香港渠务署围绕防洪减灾开展座谈交流 江西铜业股份(00358)涨4.8% 大摩料明年铜供应缺口将进一步扩大|江西铜业股份 戈壁砺锋芒,同心赴新程!财中金控以产业投行之力,携企徒文旅共启商界精英成长之旅 颐信科技洪晓彤:解决金融开源网络情报的最佳方案是“人工智能+智能人工”模式 国投丰乐:公司2018年以发行股份购买资产方式收购四川同路促进了公司种业的加速发展|资产