Talking about the harm of impurities in water to heat exchanger

1. Impurities of impurities dissolved in water by ion or molecular state
a, calcium salts The main components in water are Ca (HCO3) 2, CaCl2, CaSO4, CaSiO3 and so on. Calcium salts are the main component of the heat exchanger fouling. Among them, CaSO4 is a hard, fine crystal scale with loose structure and low adhesion. It is a relatively soft sludge. It has fluidity separated from water and is easy to remove even if it is attached to the heated surface.
b, the main components of magnesium salt in water are Mg (HCO3), MgCl2, MgSO4 and so on. After the magnesium is dissolved in water, it forms a Mg(OH)2 precipitate after being thermally decomposed, and Mg(OH)2 is also a sludge-type scale. MgCl2, MgSO4 dissolved in water, at pH <7, causes acid corrosion of the metal wall due to hydrolysis.
c, sodium salt mainly composed of NaCl, Na2SO4, NaHCO3 and so on. NaCl does not form scale, but there is free oxygen in the water, which will accelerate the corrosion of the metal wall; if the content of Na2SO4 is too high, salt will be formed on the accessory behind the evaporator, which will affect the safe operation; the effect of NaHCO3 in water on temperature and pressure Under the decomposition of NaCO3, NaOH, CO2, the metal grains will be damaged.
2, the harm of dissolved oxygen gas
Heat exchangers have many causes of corrosion, but the most severe corrosion, the fastest is oxygen. On the atomic order table, the potential of iron is above hydrogen. In neutral water without oxygen, the iron atoms on the surface of the system metal lose electrons into divalent ions (Fe-2e & rarr; Fe2+), Fe2+ ions and OH in water. - Ions bind [Fe2++2OH-→Fe(OH)2] under electrostatic attraction and establish the following balance in water:
Fe2++2OH-=Fe(OH)2 When oxygen is present in the water, Fe(OH)2 is further oxidized to insoluble iron hydroxide precipitated:
4Fe(OH)2+O2+2H2O→4Fe(OH)3↓ Due to the precipitation of Fe(OH)3, the iron ions around the anode are transferred into the aqueous solution, which accelerates the corrosion.
From the above reaction, it can be seen that water and oxygen are necessary conditions for corrosion, the anode part is the corroded part, and the cathode part is the part where the corrosion product is piled up. When the corrosion is carried out substantially uniformly over the entire surface of the metal, the rate of corrosion is not so fast, so the hazard is not large, and the corrosion is called general corrosion. When corrosion is concentrated on certain parts of the metal surface, it is called localized corrosion. The local corrosion rate is very fast, and it is easy to wear through. The pit corrosion is a common local corrosion in the heat exchanger, so the damage is very great.
3. Harm of impurities in the colloidal state on the heat exchanger
a, the main component of iron compounds is Fe2O3, which will form iron scale. When the water contains more iron compounds, the water is often yellow.
b, microbes due to air conditioning cooling circulating water water temperature, dissolved oxygen, nutrients and other micro-organisms provide conditions conducive to reproduction, microorganisms will breed and breed. Microorganisms are derived from soil and air. When the temperature of the cooling circulating water is high, the oxygen is increased by aeration in the cooling tower. Phosphate and other chemicals are often added to the water, which is just the microbial nutrient. The cooling tower is mostly located in the In the open air, sunlight is good for algae growth. The reproduction of microorganisms not only blocks the passage of the plates, but also blocks the pipes and corrodes the metal.
c, sludge in the sludge cooling circulating water, from the dust in the air and suspended matter in the supplementary water. During the convective exchange of air and water, a large amount of air is sprayed with circulating water in the tower, so that the dust enters the water and is gradually deposited in the heat exchanger with a lower flow rate.
d, slime is mainly caused by the secretion of microbes and the sediment, corrosion products, algae residue in the water, they often adhere to the wall of the heat exchanger, producing a variety of organic acids, This acid can also cause corrosion.
Therefore, the water quality requirements of the heat exchanger are very important. In the operation management, it should be emphasized, equipped with some necessary anti-scaling and anti-corrosion equipment to extend the service life of the equipment.
2019/05/11 08:50:41 3985 Click

江苏徐州一交警处置交通事故时被撞因公殉职 网易庞大智:在高水平的游戏产品面前,文化是没有边界的|网易 数盒科技“文化猫”重磅亮相海南国际电影节,领航数字版权出海 科技赋能养老投资,打造智能投资管理新标杆——工银瑞信基金荣膺中国人民银行金融科技发展奖 《阿凡达3》票房遇冷,博纳影业跌停|博纳影业 紫天科技(300280)涉嫌信披违规,受损投资者或可索赔 快报道瑞茂通控股股东7.37亿股被轮候冻结,占其持股的132.85%|瑞茂通 轻工:ECM:医美新势力,大有可为|华西证券 世名科技:截至2025年11月28日股东人数为18665户|世名科技 湘创客|澳门青年龙凡:给澳门青年打造家“湘” 美国得州大学亮相全球首台第六代咖啡机器人COFE+ 郑州新郑国际机场:年货邮吞吐量首次突破100万吨 中央经济工作会议中的“十五五”名词:海洋经济高质量发展 新交所证券市场欢迎扬子江海事发展有限公司于主板上市 加拿大消费疲软强化降息预期,美元兑加元在1.3800附近维持强势|美元 欧洲股市再创新高 政策乐观情绪延续 广西国资拟入主东方智造,控制权将变更!下周一复牌|物流 11月普惠金融-景气指数:融资环境改善,企业经营韧性凸显 港股新基金上演资金突围 提前结募火速建仓|港股 印度与新西兰敲定自由贸易协定 着眼经济增长 药明康德再引关注,长跑型资产的配置价值仍清晰